B-65270EN/05 2. SETTING αiS/αiF/βiS SERIES SERVO PARAMETERS
- 51 -
Alarm
detail No.
Parameter No.
(Series 15i)
Parameter No.
(Series 30i, 16i,
and so on)
Cause Action
10113 1707#0 2013#0
This error occurs if the specified
current cycle does not match the
actual setting.
An axis for which HRV3 is specified
exists on the same optical cable.
Review the placement of the
amplifier, or disable HRV3.
→ See Supplementary 2.
1707#0 2013#0
This alarm is issued when the axis
supports HRV3 but the other axis of
the pair does not support HRV3.
Eliminate the cause of the disability
in setting the other axis.
Alternatively, cancel the HRV3
setting.
→ See Supplementary 2.
10123
1707#0
1708#0
2013#0
2014#0
When HRV4 is set, this alarm is
issued if any of the following
conditions is met. (FS30i only)
- Servo software not supporting
HRV4 is used.
- The same FSSB system includes
axes with HRV4 setting and axes
with HRV2 or HRV3 setting.
- The limitation in the number of axes
is not observed.
(In HRV4 control, one axis/DSP is
set.)
Eliminate the causes listed on the
left. Alternatively, cancel the HRV4
setting.
→ See Supplementary 2.
10133
(*4)
1707#0
1708#0
2013#0
2014#0
This alarm is issued when HRV3 or
HRV4 is set, but the amplifier does
not support these control types.
HRV3 or HRV4 is unusable for the
axis on which the error occurred.
→ See Supplementary 2.
* The alarms indicated by "(FS30
i only)" may be issued only when
servo software Series 90D0 or 90E0 is used. When other servo
software series are used, these alarms are not issued.
Supplementary 1: Details of illegal settings of learning control parameters
For the Series 16i and so on, reset parameter No. 2115 to 0, and set
parameter No. 2151 to 1913, and then change the value of diagnosis
information (DGN) No. 353 to binary form. If a resulting binary bit is
1, its bit position indicates the detail cause. (For the Series 15
i, no
learning control is available.)
Bit position Cause
B3 The band stop filter setting (No. 2244) is out of the valid range.
B4 The profile number setting (No. 2233) is out of the valid range.
B5 The command data cycle setting (Nos. 2243, 2236, 2238, 2240, and 2266) is out of the valid range.
B6 The total of the profiles (No. 2264) is out of the valid range.
B7 G05 was started during memory clear processing.
B8 The profile number (No. 2233) was 0 when the total of profiles (No. 2264) is nonzero.
B9
An automatically set value for thinning-out shift was out of the valid range because of a long command
data cycle.