B-65270EN/05 2. SETTING αiS/αiF/βiS SERIES SERVO PARAMETERS
- 49 -
Alarm
detail No.
Parameter No.
(Series 15i)
Parameter No.
(Series 30i, 16i,
and so on)
Cause Action
1393 1762 2139
The AMR offset value of a linear
motor exceeds ±45.
Keep the setting of this parameter
within ±45. Alternatively, set bit 0
of parameter No. 2683 (for the
Series 15i) or bit 0 of parameter
No. 2270 (for the Series 30i, 16i,
and so on) to 1 to increase the
setting range of the AMR offset,
and then specify the parameter
anywhere within ±60.
1446
1447
1448
1767 2144
In the cutting feed/rapid traverse
FAD function, the feed-forward
coefficient for cutting overflowed.
Use the position gain expansion
function.
→ See Supplementary 5.
1454
1455
1456
1459
1768 2145
In the cutting feed/rapid traverse
FAD function, the velocity
feed-forward coefficient for cutting
overflowed.
Decrease the velocity feed-forward
coefficient.
1493 1772 2149
A value greater than 6 is specified in
this parameter.
Only 6 or less can be specified in
this parameter. Change the setting
to 6 or below 6.
1503 1773 2150
A value equal to or greater than 10 is
set.
Set a value less than 10.
1793 2622 2179
A negative value or a value greater
than the setting of parameter No.
1821 (Series 16i and so on) or
parameter No. 1896 (Series 15i) is
set.
Set a positive value less than the
setting of parameter No. 1821
(Series 30i, 16i, and so on) or
parameter No. 1896 (Series 15i).
1853 2628 2185
A negative value or a value greater
than the setting of parameter No.
2023 (Series 16i and so on) or
parameter No. 1876 (Series 15i) is
set.
Set a positive value less than the
setting of parameter No. 2023
(Series 30i, 16i, and so on) or
parameter No. 1876 (Series 15i).
2243 2612#5 2224#5
Series 15i : No.2612#5=1 and Series
16i and so on : No.2224#5=1
(feed-forward timing adjustment
function overflow alarm ignored) were
specified and a nano interpolation
command was issued.
Use either one.
2713 1707#0 2013#0
The PDM is used, but the HRV3
function bit is off.
Set the HRV3 function bit to 1.
3423 2755 2342
A negative value or a value equal to
or greater than 101 is set.
Set a positive value less than 100.
3433 2756 2343 A value not within -180 to 180 is set. Set a value within -180 to 180.
8213 1896 1821
A positive value is not set in the
reference counter capacity
parameter.
Set a positive value in this
parameter.
8254
8255
8256
1825 1825
The internal value of the position
gain overflowed.
Use the "position gain precision
optimization function" or the
"position gain increment function".
→ See Supplementary 5.