B-65270EN/05 4.SERVO FUNCTION DETAILS
- 191 -
The procedure for this adjustment is similar to the
procedure for adjusting observer-related
parameters in the unexpected disturbance torque
detection function (Subsection 4.12.1). Make an
adjustment by following steps <4> to <7> in (3),
"Parameter adjustment methods", in Subsection
4.12.1 in this parameter manual. When the
unexpected disturbance torque detection function
is used, and the adjustment has already been
made, re-adjustment is not needed.
1859 (FS15i)
Observer parameter (POA1)
2047 (FS30i, 16i)
[Setting value] Adjusted value (Make an adjustment according to steps <4> to <6> in
(3) in Subsec. 4.12.1.)
1980 (FS15i)
Torque offset parameter
2087 (FS30i, 16i)
[Setting value] Adjusted value (If the center of an estimated disturbance value does
not become zero on an axis such as the gravity axis, make an
adjustment according to step <6> in (3) in Subsec. 4.12.1.)
<8> Adjusting the first stage acceleration
Specify the following parameters.
1860 (FS15i)
First stage backlash acceleration amount (%)
2048 (FS30i, 16i)
[Unit of data] % (Backlash acceleration amount necessary to reverse the torque that
is equal to the friction torque in amount is assumed to be 100%.)
[Typical setting] 50 (Normally, optimum values range from 20% to 70%.)
To set a backlash acceleration amount of 0, -100 needs to be set.
Current friction torque
-100%
0
Acceleration amount when the
direction of feed is reversed