B-65270EN/05 2. SETTING αiS/αiF/βiS SERIES SERVO PARAMETERS
- 41 -
[Setting reference counter capacity]
1896 (FS15i)
Reference counter capacity
1821 (FS30i,16i)
Set the number of pulses per detector (detection unit) or a fraction of
the integer value indicating the number of pulses per detector.
(Example of parameter setting)
[System configuration]
• The Series 30i is used.
• The detector used is the CZi1024S
• The least input increment of the controller is 1/1000 deg.
• Gear ratio 1:1
[Parameter setting]
Flexible feed gear (N/M) = 360,000/1,000,000=9/25,
so parameter No. 2084 = 9, and parameter No. 2085 = 25
Number of position pulses = 12500
Reference counter capacity = 360,000