4.SERVO FUNCTION DETAILS B-65270EN/05
- 256 -
4.11.6 Overall Use of the Quick Stop Functions
To sum up, setting up the following parameters as stated can reduce
the stop distance for an emergency stop, separate detector hardware
disconnection, and OVL and OVC alarm occurrence.
<1> Specify the unexpected disturbance torque detection option.
<2> Specify quick stop type 2 at emergency stop.
<3> For a vertical axis, specify the function for lifting up a vertical
axis at emergency stop, if required.
<4> For full-closed loop axes, specify the quick stop function for
hardware disconnection of separate detector. Also if they are
subjected to synchronous control, set the HD2O bit.
<5> Specify the quick stop function at the OVC and OVL alarm.
<6> Set the brake control function bit and the brake control timer.