3. ADDRESS
B–61863E/15
PMC SEQUENCE PROGRAM
94
Specify 0 to 12 in [GROUP].
For details on how to assign [BASE] and [SLOT], see 3.2.2 Assignment
of I/O Module Addresses.
CAUTION
1 Addresses X96 to X127 and Y96 to Y127 cannot be used
in ladder diagrams.
2 When addresses X96 to X127 and Y96 to Y127 are
assigned, I/O points are not linked.
3 Connect the laser group to the end of the I/O link.
4 The I/O Link restart function cannot be used.
5 The OVERRIDE mode of the forced I/O function cannot be
used.
6 PMC–SB5 does not support a laser.
To assign connection panel I/O and operator’s panel I/O modules to the
I/O Link, set the group number with an I/O Link serial number (use a
smaller number toward the I/O Link master CNC, like 0, 1, and 2). Also,
set the base number and slot number to 0 and 1, respectively. If a
combination of the basic module and expansion modules is used as the
connection panel I/O module, assign all the modules in one I/O Link
group as one unit. Unlike the I/O Unit MODEL–A, it is unnecessary to
specify a slot number. An assignment example is shown below.
CNC
JD1A
MPG
MPG
Example
72 input points (16 general–purpose points + 56 matrix points) and
56 output points (X4 and higher, Y0 and higher)
Operator’s panel I/O
module
A20B–2002–0470
JD1B
JD1A
96 input points and 64 output points (X20 and higher, Y10 and higher)
Connection
panel I/O
basic module
JD1B
JD1A
Expansion
module 1
Expansion
module 2
Expansion
module 3
24 input points and 16 output points (X100 and higher, Y100 and higher)
Connection
panel I/O
basic module
JD1B
JD1A
Method of Assignment
3.2.7
Distribution I/O
Connection I/O Module
and Distribution I/O
Operator’s Panel I/O
Module Assignment
Methods
Assignment example