B–61863E/15
3. ADDRESS
PMC SEQUENCE PROGRAM
105
104ms 96ms
R9091. 5
200ms
504ms 496ms
R9091. 6
1 second
(7) RUN to STOP Transition Signal, STOP to RUN Transition Signal
and RUN Status Signal (PMC–SB7)
(a) Overview
(i) “RUN to STOP transition signal” and ”STOP to RUN
transition signal”
The “RUN to STOP transition signal” and the ”STOP to RUN
transition signal” for LADDER program execution are to
handle these events in a LADDER program.
(ii) “RUN status signal”
“RUN status signal” is to notify the status of LADDER and
PMC C program execution to other systems or programs, such
a network board, C executor program, FOCAS1 Ethernet or
HSSB library etc.
(b) Address
R9015.0:“STOP to RUN
transition signal”
(LADDER program use only)
R9015
76543210
R9015.1:“RUN to STOP
transition signal”
(LADDER program use only)
R9091
76543210
R9091.2:“RUN status signal”
0 : LADDER is stopping.
1 : LADDER is running.