3. ADDRESS
B–61863E/15
PMC SEQUENCE PROGRAM
62
X 127. 7
Bit number (0 to 7)
Address number (within four numerics after alphabet)
An alphabet must be specified at the beginning of the address number
to indicate the type of the signal as shown in Table 3. When
specifying the address in the byte unit by the functional instruction,
specify X127. In this case, “.” and the bit number are not necessary.
Table 3 Alphabetic characters in address numbers (1)
Model
Character Signal description Power Mate - D Power Mate- F Power Mate- H
PMC PA1 PMC- PA3 PMC- PA3 PMC- PA3
X Signal from the machine to the
PMC (MT to PMC)
X0 to X127
(I/O Link Master)
X1000 to X1003
(Built–in l/O Card)
X1020 to X1051
(I/O Link Slave)
X1000 to X1005
X1020 to X1027
(Slave)
X0 to X127
(I/O Link Master)
X1000 to X1003
(Built–in I/O Card)
X1020 to X1051
(I/O Link Slave)
Y Signal from the PMC to the
machine (PMC to MT)
(Caution 3)
Y0 to Y127
(I/O Link Master)
Y1000 to Y1002
(Built–in I/ O Card)
Y1020 to Y1051
(I/O Link Slave)
Y1000 to Y1003
Y1020 to Y1027
(Slave)
Y0 to Y127
(I/O Link Master)
Y1000 to Y1002
(Built–in l/O Card)
Y1020 to Y1051
(I/O Link Slave)
F Signal from the NC to the PMC
(NC to PMC)
F0 to F255
F1000 to F1255
(Two–path control)
F0 to F255 F0 to F255
G Signal from the PMC to the NC
(PMC to NC)
G0 to G255
G1000 to G1255
(Two–path control)
G0 to G255 G0 to G255
R Internal relay (Caution 1) R0 to R999
R9000 to
R9099
R0 to R999
R9000 to
R9117
R0 to R999
R9000 to R9117
R0 to R999
R9000 to R9117
A Message request signal A0 to A24 A0 to A24 A0 to A24
C Counter C0 to C79 C0 to C79 C0 to C79
K Keep relay (Caution 2) K0 to K19 K0 to K19 K0 to K19
T Variable timer T0 to T79 T0 to T79 T0 to T79
D Data table D0 to D1859 D0 to D1859 D0 to D1859
L Label Number – L1 to L9999 L1 to L9999 L1 to L9999
P Subprogram Number – P1 to P512 P1 to P512 P1 to P512
CAUTION
1 R9000 to R9117 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.
2 K17 to K19 are areas reserved for the PMC system
program; these areas cannot be used for output by a
sequence program.
3 I/O Link Master function is not available in the Power
Mate–MODEL F.
You cannot use the address X0–127 and Y0–127.