B–61863E/15
6. LADDER DIAGRAM MONITOR
AND EDITOR
PMC–NB6 MANIPULATION
737
Error message Meaning and solution
NO WRITE COIL.
Meaning:
Write coil is necessary, but is not found.
Solution:
Add proper write coil.
SP IN BAD LEV-
EL.
Meaning:
SP is found in wrong place.
Solution:
SP can be used at top of a subprogram. Correct it so
that no SP exists in other place.
SP IN LEVEL3.
Meaning:
SP is found in level 3.
Solution:
If END3 is located wrong, move it to correct position.
If the SP is unnecessary, remove it.
SP/SPE IN COM.
Meaning:
SP or SPE is found between COM and COME.
Solution:
If COME is missing, add it in proper position. If the
COM is unnecessary, remove it.
SP/SPE IN JMP.
Meaning:
SP or SPE is found between JMP and JMPE.
Solution:
If JMPE is missing, add it in proper position. If the
JMP is unnecessary, remove it.
SPE WITHOUT
SP.
Meaning:
There is no SP that corresponds to this SPE.
Solution:
If SP is missing, add it in proper position. If the SPE is
unnecessary, remove it.
TOO MANY LBL.
Meaning:
There are too many LBLs.
Solution:
Remove unnecessary LBLs. If this error still occurs,
adjust the construction of program to use less LBLs.
UNAVAILABLE
INSTRUCTION.
Meaning:
Unsupported instruction for this PMC model is found.
Solution:
Confirm that this LADDER program is correct one. If
this program is correct one, all these unsupported
instructions have to be removed.