H. CONNECTING THE OPERATOR’S
PANEL FOR FS 0 WITH FS16,
FS18, FS21, OR Power Mate
B–61863E/15
APPENDIX
1506
4) Specify bit image addresses. For example, to specify R900 and
R910, enter R900,R910 and press the [NL] key.
Then, the current display returns to the original parameter menu, and
the following message appears:
: : :
03 OPERATOR PANEL ; YES
KEY/LED ADDRESS ; X0000/Y0000
KEY/LED BIT IMAGE ADRS. ; R0900/R0910
: : :
CAUTION
1 After the above procedure, the addresses in Tables 3.1,
3.2–A, and 3.2–B are defined as the following PMC
addresses:
Xn → X0000 Rk / Rl →R0900/R0910
Xn+1 → X0001 Rk+1 / Rl+1→R0901/R0911
Xn+2 → X0002 Rk+2 / Rl+2→R0902/R0912
Rk+3 / Rl+3→R0903/R0913
Ym → Y0000 Rk+4 / Rl+4→R0904/R0914
Rk+5 / Rl+5→R0905/R0915
Rk+6 / Rl+6→R0906/R0916
Rk+7 / Rl+7→R0907/R0917
2 Since the PMC addresses for the I/O card are already fixed,
specify the signals to be used at the fixed addresses.
To use X1000, X1001, X1002, and Y1000 for key switches and LEDs,
enter the following:
SET KEY/LED ADDRESS(KEY ADRS., LED ADRS.)
ADDR= X1000,Y1000 [NL]
Examples