3. ADDRESS
B–61863E/15
PMC SEQUENCE PROGRAM
106
(c) Behavior
LADDER execution RUN
STOP
R9015.0
“STOP to RUN signal”
R9015.1
“RUN to STOP signal”
R9091.2
“RUN status signal”
1
0
1
0
1
0
One Scan
of LADDER
(i) “STOP to RUN transition signal” (R9015.0)
When a STOP to RUN event is detected on system software,
this signal will be turned on during the 1st scan of LADDER
program after LADDER started. This signal has individual
status corresponding the scan of each LADDER execution
level like R9000. This signal is completely turned on during
whole of the 1st scan in any execution level of LADDER
program.
– When does a STOP to RUN event happen?
– LADDER starting at every power on cycle
– Pressing a ”RUN” soft–key on a PMC screen
–“RUN” commanded by FANUC LADDER–III or
LADDER EDITING PACKAGE
Referring this signal in a LADDER program, you can recognize
and handle a ”STOP to RUN” transition event. You can program
a pre–processing for LADDER execution.
NOTE
This signal is available only in LADDER program. Don’t refer
this signal on other systems or programs, such a network
board, C executor program, FOCAS1 Ethernet or HSSB
liberally etc. because this signal has individual status in
each LADDER execution.
(ii) “RUN to STOP transition signal” (R9015.1)
When a RUN to STOP event is detected on system software, this
signal will be turned off during the last scan of LADDER
program before LADDER stopped. This signal has individual
status corresponding the scan of each LADDER execution level
like R9000. This signal is completely turned off during the last
scan before any execution level of LADDER program stops.
– When does a RUN to STOP event happen?
– Pressing a ”STOP” soft–key on a PMC screen
–”STOP” commanded by FANUC LADDER–III or
LADDER EDITING PACKAGE