G. SIGNAL ADDRESS CONVERSION
(FROM THE PMC–MODEL L/M TO
THE PMC–MODEL SB/SC)
B–61863E/15
APPENDIX
1496
The above operation terminates the conversion. Check the converted
program. If an error occurs in the conversion, modify the program.
Enter 1 on the programmer menu to change the screen to the screen for
editing a sequence program. Editing operation is the same as usual.
NOTE
Some addresses not converted have no error indication.
After modifying the program, check that all addresses are
correct according to the signal conversion table and the
connecting manual.
(1) When the Series 0 and 16 differ in the number of parameters used in
a functional instruction
Because the Series 0 and 16 differ in the numbers of parameters used
for TMR (timer), TMRB (timer), and CTR (counter), errors are
indicated at the parameters. Check the program, then delete the
parameter. Set the timer and counter again.
(2) When an address not used in functional instructions is specified
When an address used in the ladder program for the Series 0 is not
defined in the Series 16, the messages (NO PARAMETER) and
#PARAM.ERROR# appear as follows. Set the parameter again and
delete the latter message.
Example
00001 RD XXX.X
00002 SUB 8
00003 XXXX
00004 XXXX
00005 XXXX
00006 (NO PARAMETER) Set the parameter again.. .
00007 #PARAM.ERR# Delete the message. This. . . . .
message may not appear.
(XXX.X and XXXX are addresses and values.)
(3) Deleting SUB48 (END3) (In the PMC–SB)
If SUB48 (END3) is specified in the PMC–SB, an error occurs
because the PMC–SB is not provided with SUB48 (END3). When
this error occurs, delete third–level programs, or change the
third–level programs to second–level programs and delete SUB48.
(4) Address conversion for signals not listed on the signal conversion
table Modify the address for a signal by referring to the connection
manual.
G.4
MODIFYING THE
CONVERTED
SEQUENCE
PROGRAM
G.4.1
Modification Procedure