3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN)
B–61863E/15
PMC–NB6 MANIPULATION
676
(2)Override Mode
In this mode, the ladder program and the I/O devices does not
overwrite the signals which are forced to be changed. You can specify
the override mode into arbitrary X/Y addresses. The X/Y addresses in
which is not set the override mode is in the forcing mode.
Ex) I/O UNIT–MODEL A is connected with X0. And X0 is forced
to be changed.
I/O Unit–MODEL A NC
X0 = FFh X0 = FFh
D The X0 is forced to 00h
I/O Unit–MODEL A NC
X0 = FFh X0 = 00h
I/O Unit–MODEL A NC
X0 = FFh
X0 = FFh
D X0 is set in Override mode.
The input value from the I/O UNIT–MODEL A is disabled.
Therefore, the forced I/O function for X addresses in the Override mode
can be used to debug the ladder program with some I/O devices. If you
set the override mode into Y addresses, The value forced to be changed
is output to the I/O devices.