B–61863E/15
5. FUNCTIONAL INSTRUCTIONS
PMC SEQUENCE PROGRAM
297
In 15–TT, set command data in first CTL+0 – +7 by the same data form
as G112–119 of BMI interface. The data output from NC is written in
CTL+8 – +15 in the same data form as BMI interface F112–119.
CTL+0
+1
+2
+3
+4
+5
+6
+7
+12
+13
+9
EISTB, EOREND etc
CTL+8
EOSTB, EIREND etc
EIA0 to EIA7
EOA0 to EOA7
EID32 to EID39 +10
EOD32 to EOD39
EID40 to EID47
+11
EOD40 to EOD47
EID0 to EID7
EOD0 to EOD7
EID8 to EID15
EOD8 to EOD15
EID16 to EID23 +14
EOD16 to EOD23
EID25 to EID31 +15
EOD25 to EOD31
to to
to to
NOTE
Refer to the following manuals in detail of BMI interface.
“FANUC Series 15–MODEL B Connection Manual (BMI
interface)”
“FANUC Series 15i/150i–MODEL A Connection Manual
(Function)”
This indicates end of transfer of external data. This transfer end condition
shows the end of a series of external data input sequence. This functional
instruction executes a series of transfer sequence, and finally sets ESTB
= 0 in the PMC ³ NC interface. As a result, W1 is set to 1 (W1 = 1) after
confirming that EREND = 0.
When W1 = 1, transfer of data is over. Reset ACT now.
CAUTION
1 The EXIN command cannot input multiple external data items
at the same time. Be sure to issue the next EXIN command
(ACT = 1) after external data transfer ends (W1 = 1).
2
Be sure to specify an interlock when the external data input function
is used by commands other than the function commands, DISP,
DISPB, and EXIN.
5.45.5
End of Transfer (W1)