B–61863E/15
3. DISPLAYING PMC INPUT/OUTPUT
SIGNALS AND INTERNAL RELAY
(PMCDGN)
PMC–NB6 MANIPULATION
677
CAUTION
1 In the Override mode, the refresh cycle of the I/O signal is 8msec, which is synchronized with
the 1st level of the ladder program. Usually, the refresh cycle of the I/O link is 2msec. So, the
timing of the signals for I/O devices is delayed. Pay attention the change of work of the ladder
program which depends on the timing of the I/O devices.
2 The processing time of the 2nd level of the ladder program might get longer in the override
mode.
3 The relay coils which are set in the override mode are displayed as the processing result of the
ladder program in the ladder monitor screen. The output value for the I/O devices is forced to
be changed. Pay attention that the values on the ladder monitor screen does not correspond
with the output values for the I/O devices.
Ex.): I/O UNIT–MODEL A is connected with Y0. And Y0.0 is forced to be changed.
Usually, the display values on the ladder screen correspond with the output values for the
I/O UNIT–MODEL A as follows.
If you set ”1” into the Y0.0 in the override mode, the value is output to the I/O
UNIT–MODEL A as follows.
I/O Unit–MODEL A NC
X0.0 Y0.0
OFF OFF
Ladder Monitor
Y0.0=OFF
OFF
I/O Unit–MODEL A NC
X0.0 Y0.0
OFF
Ladder Monitor
Y0.0=ON
WARNING
When you change the signals by the forcing I/O function, you have to pay special attention.
Inappropriate use of this function may cause unexpected reaction of machine. You have to
make it sure that nobody is near the machine when you use this function.