ALARM NOTHING
or
NO ALARM (In case of PMC–NB6)
Normal status
ER00 PROGRAM DATA ERROR (ROM) The sequence program in the ROM is not written correctly.
(solution) Please exchange ROM for the sequence program.
ER01 PROGRAM DATA ERROR (RAM) The sequence program in the debugging RAM is defective.
(solution) Please clear the debugging RAM and input LADDER again.
The debugging RAM is not installed though the RAM is selected.
(solution) Please install the debugging RAM or install ROM for sequence
program and select ROM with K17#3=0.
ER02 PROGRAM SIZE OVER The size of a sequence program exceeded the maximum allowable
ladder size.
(solution) The ordered RAM size is smaller than the option. Contact FA-
NUC.
Change the value of MAX LADDER AREA SIZE on the SYSPRM
screen, then turn the power off then back on (only with PMC–SC).
ER03 PROGRAM SIZE ERROR (OPTION) The size of sequence program exceeds the option specification size.
(solution) Please increase the option specification size.
Or, reduce the size of sequence program.
ER04 PMC TYPE UNMATCH The PMC model setting of the sequence program is not corresponding to
an actual model.
(solution) Please change the PMC model setting by the offline program-
mer.
ER05 PMC MODULE TYPE ERROR The module type of the PMC engine is not correct.
(solution) Please exchange the module of PMC engine for a correct one.
ER06 PROGRAM MODULE NOTHING Both ROM for sequence program and the debugging RAM do not exist
(PMC–SC only).
For a 3–path system, the PMC model must be SB6.
(solution) Contact FANUC.
ER07 NO OPTION (LADDER STEP) There is no step number option of LADDER.
ER08 OBJECT UNMATCH Sequence Program has 2 channels of I/O Link, but PMC control software
or Ladder Editor Card or PMC C language control software does not
support the I/O Link expansion.
(solution) To use only the I/O Link channel 1, use sequence program for
only channel 1. To use the I/O Link channel 2, update PMC
control software and Ladder Editor Card and PMC C language
control software supported the I/O Link expansion.
ER09 PMC LABEL CHECK ERRORPLEASE
TURN ON POWER AGAIN WITH PUSH ’O &’ Z’.
(CLEAR PMC SRAM)
With a change in the PMC type, for example, the retention–type memory
of the PMC must be initialized.
(solution) 1) Press and hold down the ’O’ and ’Z’ key combination, and
turn the CNC back on.
2) When an alarm occurred on the loader control side, press
and hold down the ’5’ and ’Z’ key combination, and turn the
CNC back on.
3) Replace the backup battery.
4) Replace the master printed circuit board.