B–61863E/15
9. SEQUENCE PROGRAM
STRUCTURING
PMC SEQUENCE PROGRAM
389
a) DISPB
b) EXIN
c) WINDR (only low-speed response)
d) WINDW (only low-speed response)
e) MMCWR
f) MMCWW
g) MMC3R
h) MMC3W
When you use the above-mentioned functional instructions, ACT=1 must
be held until the transfer completion information(W1) becomes 1.
Therefore, be careful of the following when using those instructions in
subprograms.
D Do not stop calling the subprogram at the state which has not been
completed yet, that is executed still while using the instructions in the
subprogram.
(In other words, do not set the ACT of the CALL instruction to 0)
³ If you do it the function of the instructions after that is not
guaranteed.
D Call the subprogram from other subprograms at the state which has
not been completed yet while using the instructions in the
subprogram.
³ The movement of the above-mentioned functional instruction
after that is not guaranteed so that the last functional instruction
may be processing the instruction.
Then, when the subprogram, in which the above-mentioned functional
instruction is used, is called from two or more places, it is necessary to
control the subprogram exclusively. The case of the WINDR instruction
(low-speed response) is given as an example here.
9.3
CAUTIONS FOR