B–61863E/15
5. FUNCTIONAL INSTRUCTIONSPMC SEQUENCE PROGRAM
209
(a) Number of turned–off coils
Specify 0 to 9999.
0 : Region specification
Other than 0: Coil number specification
W1
W2
A B
D
C
EF G
W3
ACT
ACT
Fig. 5.18.3 (a) Relay circuit example
CAUTION
1 A functional instruction in a range specified by COM executes processing,
regardless of COM ACT. However, if COM ACT=0, the coil of the execution result becomes 0.
2 Another COM instruction cannot be specified in the range specified by the COM instruction.
3 If COM ACT=0, the coil written in by a WRT. NOT instruction in a range specified by COM
becomes 1 unconditionally.
4 The number of coils cannot be specified for other than PMC–SB/SC. Assume the number of
coils to be 0 and specify the region with the common line control end (COME) command.
W1
COM
ACT
3
Regardless of the ACT condition of the
COM instruction, if ACT1=1, the input
data of MOVE function is transferred to
the output address
W2
B
D
C
E
W3
MOVE
High–ord
er 4–bit
logical
multiplicat
ion data
Low–orde
r 4–bit
logical
multiplicat
ion data
Input
data
address
Output
address
ACT2
COIN
Reference
data
(address)
Comparis
on data
(address)
ACT1
When ACT=0 in the COM instruction,
W2=0 unconditionally.
A
Fig. 5.18.3 (b)
5.18.3
Parameter